Power Limited Cables
Paige fire alarm cables are designed for a wide range of applications
in low voltage fire alarm systems. They carry the following listings in common:

75°C Temperature rated
300 volt
UL Listed and Canadian UL Listed
Most are dual listed to also meet NEC Articles 760 permitting
cross application in sound and security systems
Meet NEC Articles 800 and 725

Dual NEC / UL Listings for cables in this section:
Gauge Sizes
Non-Plenum
Non-Plenum Riser
Plenum
24 AWG - 16 AWG
FPL / CM
FPLR / CMR
FPLP / CMP
14 AWG - 12 AWG
FPL / CL3
FPLR / CL3R
FPLP / CL3P
For additional information on NEC / UL click here.

Additional features of cables in this section:
Twisted conductors for reduced cross-talk
ASTM bare copper conductors
Premium grade PVC for improved strength and flexibility
When shielded, corrosion resistant tinned copper drain wires are used
Color-coded conductors

Cables Installed in Raceway
For maximum installation flexibility, Paige offers a series of TFN and THHN,
600 volt cables, permitted for use in power limited fire alarm circuits under NEC Article 760.52 "Wiring Methods and Materials on Load Side of the PLFA Power Source" and sub-section 760.52(A) "NPLFA Wiring Methods and Materials". When installed in accordance with NEC Chapter 3, these cables deliver a number of speedy installation advantages:

Rated TFN (18 and 16 AWG) or THHN (14 and 12 AWG)
90°C dry / 75°C wet
Rated 600 volts
Available in singles or Easy-pull pre-twisted, color-coded pairs
Available in flexible metal armor